Loading
MultiCon devices are versatile controllers with a capability of measuring and data logging simultaneously.
Powerful and versatile data-loggers.

CMC-99-PS32/ACM/R45/E/D8-101

  • MultiCon = Meter + Controller + Recorder + HMI + SCADA in one package
  • stable firmware based on Linux
  • 27 available input/output modules
  • 60 logical channels
  • colour LCD display 3.5" TFT, with touchscreen
  • recording data with maximum speed 10Hz (ten samples per second)
  • 4 GB internal data memory
  • RS-485 (Modbus RTU), USB Host, Ethernet communication
  • panel, compact device in 96 x 96 mm case
Details
Power supply
16...35V AC, 19...50V DC, RS-485, sensors supply 200 mA@24V DC, 1 binary input 24V DC
Slot D
ACM communication module (RS-485, RS-485/232, USB Host, Ethernet)
Slot C
R45 module (4 x SPDT relay 5A outputs)
Slot B
empty
Slot A
D8 module (8 x digital input)
Memory
4 GB
Options
no options [01]
Description

The MultiCon CMC-99 is a powerful and versatile compact-multichannel-controller with a capability to record data, if the recording function is requested and activated. Thanks to that it is one of the first industrial devices which integrates advanced control functions (PID, ON/OFF, time & profiles etc.) and logging of setpoints, excitations and current state of controlled objects. Based on Linux firmware, is stable and the touch screen makes configuration easy and comfortable and data presentation also readable and attractive. Although the MultiCon CMC-99 is build in a quite small housing, it can integrate up to 48 inputs, and its construction allows user almost free configuration by choosing up to 3 from 27 available input/output modules.

Specification
Number of inputs
48
Input type
depends on configuration:
9 universal inputs max.
48 analogue inputs max.
48 digital inputs max.
24 TC inputs max.
12 RTD inputs max.
12 counter / flowmeter / ratemeter inputs max.
1 digital input 24V DC
mixed: analogue-NTC temperature
mixed: analogue-digital
Input range
0/4...20 mA
0/1...5V, 0/2...10V
0...30V
-10...25 mV, -10...100 mV, 0…600 mV, ±25 mV, ±100 mV
0...300Ω, 0...3kΩ
Pt100, Pt500, Pt1000 (PN-EN): -100...600°C, Pt'50, Pt'100, Pt'500 (GOST): -200...600°C, Ni100, Ni500, Ni1000 (PN-EN): -60...180°C, Cu50, Cu100: -50...200°C, Cu'50, Cu'100 (GOST): -200...200°C
TC K: -200...+1370°C, S: -50...+1768°C, J: -210...+1200°C, T: -200...+400°C, N: -200...+1300°C, R: -50...+1768°C, B: +250...+1820°C, E: -200...+1000°C
0-20 (1/sec.), 0-20 (1/min.), 0-20 (1/h)
4-20 (1/sec.), 4-20 (1/min.), 4-20 (1/h)
Output type
depends on configuration:
8 analogue 4...20 mA max.
16 relay 1A/250V max.
4 relay 5A/250V max.
48 SSR max.
24V DC
Power supply
16...35V AC, 19...50V DC
85..260V AC/DC
Display
3.5 inch graphic TFT, 16-bit colour, 320 x 240 pixels, with touch screen
Memory capacity
internal 4 GB
Data recording period
from 0,1 s to 24 h with resolution 0,1 s
Communication Interface
RS-485 / Modbus RTU
USB Host port
ETU (1 or 2 x USB Host, 1 x Ethernet 10 Mb/s)
ACM (3 x RS-485/RS-232, 1 or 2 x USB Host, 1 x Ethernet 10 Mb/s)
Transmission protocol
NTP
Web Server
HTTP
Modbus RTU / Master
Modbus RTU / Slave
Modbus TCP Server
Operating temperature
0...+50°C
-20…+50°C
Protection class
IP 40 (front USB Host)
IP 54 (front USB Host + transparent door with key STD-99/141)
IP 65 (front)
optional integrated frame for panel cut-out sealing
Case material
NORYL-GFN2S E1
Mounting
panel
Case dimensions
96 x 96 x 100 mm